462. Where explosive charges are fired by means of an electric power system:
(1)  the electrical circuit shall be:
(a)  isolated and not grounded;
(b)  used only for blasting;
(2)  the blasting switch shall be designed so that:
(a)  the switch mechanism automatically returns to the open position by gravity;
(b)  the conductors leading to the charges are automatically short-circuited when the switch is in the open position;
(c)  the energized switch terminals are enclosed in a fixed metal box;
(d)  the box in which the firing conductors and the short-circuiting device are placed is provided with a door and a closing device designed so that the door can be closed only when the switch is in the open position; this door shall be kept locked except at firing time; the key shall be accessible only to the person in charge of blasting;
(3)  a disconnecting device with overcurrent protection shall be installed between the source of power and the blasting switch; a horizontal protective gap against lightning of at least 1.5 m (4.9 ft) shall be provided between the disconnecting device and the blasting switch, and the gap may be closed only at the time of firing;
(4)  the voltage of the firing device shall not exceed 220 V.